Commercial Building NYC Mail Room

A detailed AC ELF magnetic field site survey of unoccupied tenant space located on the "sub-cellar" level in a building was performed on August 10th, 2005. Data recorded inside the tenant space revealed magnetic flux density levels exceeding 422 milligauss (mG) at the 1-meter level and as high as 4400 mG right underneath the busways. Subsequently, a 6,004 ft AC ELF magnetic shielding solution was recommended to attenuate levels to 10 mG and less under all normal operating conditions.

 

 

Shielding installation began on 24 November 2005, and was completed on 18 November 2005. During the shielding installation, preliminary data was collected verify shielding performance. During this data collection, it was noted that circulating ground currents on the adjacent conduits (not originally intended for shielding) effected the overall shielding performance.

 

 

 

 

 

 

 

 

 

Shielding Pictures